FigureDesk

3-Phase Power Calculator

Enter line voltage, line current, and power factor for a balanced three-phase system. FigureDesk calculates total power and the per-phase voltage and current for either a wye (star) or delta configuration.

Your numbers

V
A

Leave blank to assume 1.0 (purely resistive).

Result

Total real power

37412.297 W

Total apparent power
41569.219 VA
Total reactive power
18119.603 var
Power per phase
12470.766 W
Phase voltage
277.128 V
Phase current
50 A

Given V_line = 480 V, I_line = 50 A, PF = 0.9 → P = √3 × V_line × I_line × PF = 37412.297443 W

How it works

A balanced three-phase system's total power depends only on line voltage, line current, and power factor — the same formula regardless of whether the load is wired wye or delta. What differs between the two is the relationship between line and phase quantities: in a wye connection, phase voltage is line voltage divided by √3 and phase current equals line current; in a delta connection, phase voltage equals line voltage and phase current is line current divided by √3. This is the part of three-phase math that actually causes confusion, so this calculator shows both together.

P = √3 × Vline × Iline × PF
Wye: Vphase = Vline / √3, Iphase = Iline
Delta: Vphase = Vline, Iphase = Iline / √3

Worked example

A 480 V line, 50 A line current, 0.9 power factor, wye-connected:

  • Total real power: √3 × 480 × 50 × 0.9 ≈ 37,412 W
  • Phase voltage: 480 / √3 ≈ 277.1 V
  • Phase current: 50 A (same as line current in wye)

Important assumptions

  • Assumes a balanced three-phase system — all three phases carry equal voltage, current, and load. Unbalanced systems need a per-phase calculation this tool does not do.
  • Power factor defaults to 1.0 (purely resistive) if left blank — real three-phase loads like motors and transformers are usually lower, so entering your equipment's actual power factor gives a meaningfully different, more accurate result.
  • Line voltage is the voltage measured between any two line conductors — not line-to-neutral voltage, which only exists in a wye system and is already computed here as "phase voltage."

FAQ

What's the difference between wye and delta?

Wye (star) connects each phase winding between a line and a shared neutral point, giving a lower line-to-neutral (phase) voltage than the line-to-line voltage — this is why residential and commercial services often distribute both 120V and 208V from the same wye system. Delta connects windings directly between pairs of lines, so line and phase voltage are equal, but phase current is lower than line current.

How is this different from the Watts to Amps Calculator?

Watts to Amps converts between total power and line current for a three-phase system in one direction, using the same underlying formula. This calculator goes further: it reports the full power breakdown (real, apparent, reactive) together with the per-phase voltage and current for whichever configuration — wye or delta — your system is actually wired in.

Why do I need to know my power factor?

Power factor is the ratio of real power (what does useful work) to apparent power (what the source has to supply). Leaving it at the default 1.0 assumes a purely resistive load; motors, transformers, and many other three-phase loads run lower — check the equipment's nameplate, or use the Power Factor Calculator if you have a real and apparent power reading instead.

What does reactive power (var) mean here?

Reactive power is the portion of apparent power that does not do useful work — it's drawn to build the electric and magnetic fields that transformers, motors, and other inductive equipment need to operate. It's calculated here from the real and apparent power you've entered (or that follow from your power factor).

FigureDesk results are advisory and do not replace a licensed electrician, a qualified engineer, or the applicable local electrical code. Verify any electrical work against your local code and with a qualified professional before relying on it.